Natural Gas Generator for Home: Sizing, Gas Supply and the Electrical Side in Minnesota
A natural gas standby generator never needs refueling, but it can burn more gas than your furnace and water heater combined. Here's how to check your meter, piping and panel before you buy.

Reviewed by John Ihle, MN Master Electrician (AM005101) · NABCEP-credentialed · iSolar, Saint Paul Park, MN · Last reviewed October 2026
The short answer: A natural gas generator for home runs on your utility gas line, but it's thirsty: Generac's 26 kW unit burns about 333 cubic feet per hour at full load, roughly 333,000 BTU. Add that to your furnace and water heater and many homes need a larger meter or bigger gas piping. Plan the gas side, transfer switch and permits together.
Why a natural gas generator for home use is popular in Minnesota
A natural gas generator for home backup connects to the same utility gas line that feeds your furnace. When the power goes out, an automatic transfer switch disconnects you from the grid, the generator starts within seconds, and it runs as long as the gas keeps flowing. No propane deliveries, no gas cans, no stale fuel.
That convenience comes with a sizing problem most buyers don't hear about until the install. Standby generators burn a lot of gas, and your meter and house piping were sized for the appliances you had when the house was built. This guide covers the gas side first, then the electrical side. For equipment and installation prices, see our separate Generac generator cost guide.
How much gas does a natural gas standby generator use?
Manufacturers publish fuel use at half and full load. Generac's 26 kW home standby unit is a useful reference because it's at the top of the air-cooled range:
| Generac 26 kW standby | Natural gas | Propane (LP) |
|---|---|---|
| Rated output | 22.5 kW | 26 kW |
| Fuel use at 50% load | 188 cu ft/hr | 75 cu ft/hr (2.06 gal/hr) |
| Fuel use at 100% load | 333 cu ft/hr | 132 cu ft/hr (3.63 gal/hr) |
| Approximate BTU/hr at full load | About 333,000 | About 330,000 |
| Required inlet pressure | 3.5–7 in. water column | 10–12 in. water column |
Two things stand out. First, natural gas output is lower: the same engine makes 22.5 kW on natural gas versus 26 kW on propane, because natural gas carries less energy per cubic foot. If you're sizing for a specific load, use the natural gas rating. Second, Generac's support guidance says fuel supply should be sized for 100% load, and gives the conversion your plumber needs: natural gas BTU per hour equals cubic feet per hour times 1,000.
Will your gas meter keep up?
CenterPoint Energy, which supplies natural gas to much of the Twin Cities, states that when you install additional appliances you may need your service line or meter relocated or resized. Its service guidelines treat 1 cubic foot per hour (CFH) as 1,000 BTU and send jobs with a total connected load over 550 CFH at standard delivery pressure into a formal design review.
Here's a worked example using typical nameplate ratings. Check your own appliance labels; yours will differ.
| Appliance | Example nameplate input | CFH |
|---|---|---|
| Furnace | 100,000 BTU/hr | 100 |
| Water heater | 40,000 BTU/hr | 40 |
| Gas range | 65,000 BTU/hr | 65 |
| Gas dryer | 22,000 BTU/hr | 22 |
| Subtotal before generator | 227,000 BTU/hr | 227 |
| 26 kW standby generator (NG, full load) | 333,000 BTU/hr | 333 |
| Total connected load | 560,000 BTU/hr | 560 |
In this example, adding the generator more than doubles the connected load and pushes it past CenterPoint's 550 CFH formal-design threshold. A smaller generator, or a home with fewer gas appliances, may stay under it. Either way, the utility, not the generator dealer, decides whether the meter and service line can carry the load. CenterPoint says it strives to install new service within 20 business days of the request, and formal design can take longer, so start that conversation early. If your gas comes from Xcel Energy or a municipal utility, ask them the same question.
House piping matters as much as the meter
Even with a big enough meter, the pipe from the meter to the generator has to deliver full flow at 3.5 to 7 inches of water column. Generac's own guidance says it can't size gas lines and points owners to the gas provider or a licensed plumber. Pipe size depends on the length of the run and the number of elbows and tees. A generator on the far side of the house from the meter may need a dedicated, larger line rather than a tee off the furnace branch.
Cold snaps: the real winter test
The worst Minnesota outages tend to come with ice storms and deep cold, which is exactly when every gas appliance runs hard at once. The furnace is firing nonstop, the water heater is recovering, and the generator is at high load because the furnace blower, well pump or sump pump are all on it. That simultaneous demand is what the 100%-load sizing rule protects against. An undersized line shows up as a generator that surges, can't hold voltage or shuts down when the furnace kicks on.
A few practical winter points:
- Keep the gas meter, regulator and generator intake clear of snow and ice. Drifts and roof runoff can block regulator vents.
- Ask your installer to verify gas pressure with the generator under load and the furnace running. Generac says manometer testing should be done by a dealer, licensed plumber or the gas utility, not the homeowner.
- Natural gas supply interruptions are rare, but they're not impossible. If you need protection for that too, a dual fuel setup or a battery covers a different risk.
Cold-weather maintenance such as battery warmers and oil changes is covered in our standby generator maintenance guide.
The electrical side of the install
The gas work gets the generator running. The electrical work decides what it powers and whether it's safe. A typical natural gas standby install includes:
- Automatic transfer switch. Either service-rated (installed at the meter, transferring the whole house) or a smaller switch feeding selected circuits. It prevents backfeeding the utility lines.
- Load calculation. We size the generator to the loads that actually start together: furnace blower, well pump, sump pump, refrigerator, and any electric heat or EV charger you expect to run. Air conditioners and well pumps have high starting current.
- Load management. If a whole-house transfer switch feeds more potential load than the generator can carry, load-shedding modules can lock out large appliances such as an AC or electric range until capacity frees up.
- Feeder and breaker. Generac's 26 kW unit lists a 110-amp main line circuit breaker, so the feeder from the generator to the transfer switch is a substantial conductor run.
- Permits. The electrical work requires a Minnesota electrical permit and inspection, and the gas piping typically needs a separate mechanical or gas permit from your city.
Our free generator sizing tool gives a starting kW number from the appliances you want to back up.
Natural gas generator vs propane vs battery
| Option | Strength | Watch out for |
|---|---|---|
| Natural gas standby | Unlimited runtime on utility gas | Meter and piping capacity; lower kW rating than on LP |
| Propane standby | Works where there's no gas main; full rated output | Tank size limits runtime; refill logistics in a storm |
| Home battery | Silent, no fuel, pairs with solar | Limited kWh for multi-day outages in cold weather |
For a side-by-side look at fuel versus storage, read generator vs battery for Minnesota outages.
Planning your natural gas generator
iSolar's electrical team installs standby generators across the Twin Cities. We look at your panel, your loads and the path from the gas meter in one visit, and we flag meter or piping questions for the utility before you're committed to a unit size. Start on our generator information page or request a quote.
Sources
- Generac — 26kW Standby Generator with Whole House Switch (model 7291) specifications
- Generac Support — How do I determine the proper fuel pressure for my air-cooled home standby generator
- Generac Support — How do I determine the fuel line sizing for my air-cooled home standby generator
- CenterPoint Energy — Meter and service upgrade tool
- Minnesota Department of Labor and Industry — Electrical permits for homeowners
Frequently asked.
How much natural gas does a home generator use?
It depends on size and load. Generac's 26 kW air-cooled standby unit burns about 188 cubic feet per hour at half load and 333 cubic feet per hour at full load. Your utility bills gas by the therm, so check your rate to estimate cost per hour.
Do I need a bigger gas meter for a standby generator?
Often, yes. CenterPoint Energy says adding appliances may require resizing the meter or service line, and loads over 550 cubic feet per hour at standard pressure go through formal design. Add up your appliance nameplates plus the generator's full-load use and ask the utility.
Is a natural gas generator better than propane in Minnesota?
Natural gas never needs refilling, which is a big advantage in a long outage. Propane gives full rated output and works where there's no gas main. The same engine produces less power on natural gas, so size accordingly.
What gas pressure does a Generac generator need?
Generac lists 3.5 to 7 inches of water column for natural gas and 10 to 12 inches for propane vapor on its air-cooled home standby units. Pressure should be tested by a dealer, licensed plumber or the gas utility.
Can a natural gas generator run during a Minnesota cold snap?
Yes, as long as the gas supply and piping can deliver full flow while your furnace and water heater also run. Keep the meter, regulator and generator clear of snow and ice.
What permits do I need for a natural gas generator?
An electrical permit and inspection for the transfer switch and wiring, and typically a mechanical or gas permit for the piping. Your installer should pull both and coordinate any meter work with the gas utility.